3 - 13
*1: The remote input refresh area indicates the area to be used when auto refresh is set to the input (X) in the
CC-Link IE controller network, MELSECNET/H, or CC-Link.
Data in the remote input refresh area will be refreshed automatically during END processing.
*2: Data in the GX Developer input area can be turned on/off by the following operation.
Test operation by GX Developer
Writing data from a network module
*3: Data in the output (Y) device memory can be turned on/off by the following operation.
Test operation by GX Developer
Refresh via CC-Link IE controller network or MELSECNET/H
Writing data from an external device using the MC protocol
Auto refresh via CC-Link
When a contact instruction for input is executed:
The CPU module performs a logical OR operation between input data from the input module 1) and
input data in the GX Developer input area 2) or data in the remote input refresh area.
Then, the module stores the result in the input (X) device memory and executes a sequence
program using the stored result as input data 3).
When a contact instruction for output is executed:
The CPU module reads output data 4) from the output (Y) device memory and executes a sequence
program.
When the OUT instruction for output is executed:
The CPU module outputs the operation result of the sequence program 5) to the output module and
also stores the result in the output (Y) device memory.
Figure 3.7 I/O data flow in direct mode
CPU module
CPU (operation
processing area)
3)
4)
*3
5)
DX0
Y20
Input (X)
device
memory
Output (Y)
device
memory
Network
module
Input
module
1)
2)
Remote
input refresh
area
*1
GX
Developer
input area
*2
DY25
Output
module