Mitsubishi Electronics QnUCPU Home Theater Server User Manual


 
CHAPTER9 DEVICES
9
2
3
4
5
6
7
8
9.14 Convenient Usage of Devices
9.14.2 Local device
9 - 87
(3) Local device setting
(a) Setting the local device range
In the Device tab of the PLC parameter dialog box, set the range that is used as a local device.
Note that the local device range is common to all programs, and cannot be changed for each program.
For example, if a local device range is specified as M0 to M100, this range setting applies to all programs that
use the local device.
The 32-bit index modification range must not overlap with the local device setting range of the index register.
If overlapped, 32-bit index modification values will be written over the local device values.
When CPU module parameters which contains local device setting of the index register are read out from the GX
Developer that does not support the setting, all of the index register data will be read out as global device data.
Figure 9.101 Device
Figure 9.102 Local device range
Program A Program B Program C
M0
M100
Local
device
Local
device
Local
device
Locla device
range is
common to all
programs.