Mitsubishi Electronics QnUCPU Home Theater Server User Manual


 
6 - 156
(5) Functions that cannot be performed during backup
Table6.55 shows functions that cannot be performed during backup.
(6) Precautions
(a) Do not perform the following operations during backup.
Mounting/removal of a memory card
Power-off of the CPU module
Reset
(b) Even if booting parameters backed up with contacts for the Universal model QCPU
having the serial number (first five digits) is "10101" or earlier, the system ignores
the parameters.
In this case, even if the backup start setup contact or backup start contact set by the
parameters is turned on, the operating status of the CPU module does not change (a
diagnostic error is not detected).
(c) After backup is ready to start, the following functions stop (do not resume the
operations even after the backup).
Refresh of network modules
Data link transfer
Auto refresh of intelligent function modules
Auto refresh of CPU shared memory
Table6.55 Functions that cannot be performed during backup
Category Function Category Function
Drive operation
Format PLC memory Trace Sampling trace registration
Write the program memory to ROM Remote operation Remote latch clear
Program memory batch transfer
File operation
Write to PLC
Arrange PLC memory Delete PLC data
Online change
Online change (ladder mode) Write PLC user data
Online change (files) Delete PLC user data
Online change (multiple blocks) Password registration
Change TC setting Latch data backup operation
Monitor Monitor condition setup
FTP function For all operations and commands
Debug Executional conditioned device test