Mitsubishi Electronics QnUCPU Home Theater Server User Manual


 
6 - 24
(4) Precautions
(a) Remote RESET in the RUN status
When the CPU module is in the RUN status, the remote RESET operation cannot be performed.
To perform the operation, change the operating status of the CPU module to STOP by the remote
STOP or similar operation.
(b) Status after reset processing
After reset processing of the remote RESET operation is completed, the CPU module will be placed
in the operating status set by the RUN/STOP/RESET switch.
If the RUN/STOP/RESET switch is set to STOP, the CPU module will be in the STOP status. If the
switch is set to RUN, the CPU module will be in the RUN status.
If the remote RESET operation is performed to the CPU module which is stopped due to an error, note
that the CPU module will be placed in the operating status set by the RUN/STOP/RESET switch after
reset processing is completed.
If the CPU module cannot be reset by the remote RESET operation from GX Developer, check that the
"Allow" checkbox for the remote RESET operation in the PLC system tab of the PLC parameter dialog box
is selected.
If the checkbox is not selected, the CPU module cannot be reset even after the remote RESET processing
from GX Developer is completed.
(c) When an error occurs due to noise
Note that the CPU module may not be reset by the remote RESET operation from GX Developer.
In this case, reset the CPU module using the RUN/STOP/RESET switch or power off and then on
the CPU module.