Mitsubishi Electronics QnUCPU Home Theater Server User Manual


 
CHAPTER6 FUNCTIONS
1
2
3
4
5
6
7
8
6.25 Initial Device Value
6 - 137
(5) Procedures and settings for using initial device values
To use initial device values, create initial device value data with GX Developer beforehand, and store the data as
a initial device value file in the program memory, standard ROM, or memory card of the CPU module.
Add an initial device value data to the project data list of GX Developer.
The Device initialization range setting screen appears. Set the initial device value range.
The number of settable points is up to 8000 points per range setting.
Add device memory data in the project data list of GX Developer.
The device memory screen appears. Set the initial device value data within the initial device value range set
above.
When changing the setting on the Device initialization range setting screen, always execute "Device memory registration/
diversion".
For details of the "Device memory registration/diversion", refer to the following.
GX Developer Version 8 Operating Manual
Figure 6.105 Device initialization range setting screen and device memory screen