Mitsubishi Electronics QnUCPU Home Theater Server User Manual


 
12 - 50
(4) Scan information
Table12.22 Special register
Number Name Meaning Explanation
Set by
(When Set)
Corres-
ponding
ACPU
D9
Corresponding
CPU
SD500
Execution
program No.
Program No. in
execution
Program number of program currently being executed is stored as BIN
value.
S (Status
change)
New
Qn(H)
QnPH
QnPRH
QnU
SD510
Low speed
excution type
program No.
Low speed
execution type
program No. in
execution
Program number of low speed excution type program No. currently
being executed is stored as BIN value.
Enabled only when SM510 is ON.
S (Every END
processing)
New
Qn(H)
QnPH
SD520
Current scan
time
Current scan time
(in 1 ms units)
The current scan time is stored into SD520 and SD521.
(Measurement is made in 100 s units. (For the Universal model QCPU,
in 1 s units.))
SD520: Stores the ms place. (Storage range: 0 to 65535)
SD521: Stores the s place. (Storage range: 0 to 900 (For the
Universal model QCPU, storage range is 0 to 999))
(Example) When the current scan time is 23.6ms, the following values are
stored.
SD520 = 23
SD521 = 600
S (Every END
processing)
D9018
format
change
QCPU
SD521
Current scan time
(in 100 s units)
S (Every END
processing)
New
SD522
Initial scan time
Initial scan time
(in 1 ms units)
Stores the scan time of an initial execution type program into SD522 and
SD523.
(Measurement is made in 100 s units. (For the Universal model QCPU,
in 1 s units.))
SD522: Stores the ms place. (Storage range: 0 to 65535)
SD523: Stores the s place. (Storage range: 0 to 900 (For the Universal
model QCPU, storage range is 0 to 999))
S (First END
processing)
New
Qn(H)
QnPH
QnPRH
QnU
SD523
Initial scan time
(in 100 s units)
SD524
Minimum scan
time
Minimum scan
time (in 1 ms
units)
Stores the minimum value of the scan time except that of an initial
execution type program into SD524 and SD525. (Measurement is made
in 100 s units. (For the Universal model QCPU, in 1 s units.))
SD524: Stores the ms place. (Storage range: 0 to 65535)
SD525: Stores the s place. (Storage range: 0 to 900 (For the Universal
model QCPU, storage range is 0 to 999))
S (Every END
processing)
D9017
format
change
SD525
Minimum scan
time (in 100 s
units)
S (Every END
processing)
New
SD526
Maximum scan
time
Maximum scan
time (in 1 ms
units)
Stores the maximum value of the scan time except that of an initial
execution type program into SD526 and SD527. (Measurement is made
in 100 s units. (For the Universal model QCPU, in 1 s units.))
SD526: Stores the ms place. (Storage range: 0 to 65535)
SD527: Stores the s place. (Storage range: 0 to 900 (For the Universal
model QCPU, storage range is 0 to 999))
S (Every END
processing)
D9019
format
change
SD527
Maximum scan
time (in 100 s
units)
New
SD528
Current scan
time for low
speed execution
type programs
Current scan time
(in 1 ms units)
Stores the current scan time of a low speed execution type program into
SD528 and SD529.
(Measurement is made in 100 s units.)
SD528: Stores the ms place. (Storage range: 0 to 65535)
SD529: Stores the s place. (Storage range: 0 to 900)
S (Every END
processing)
New
Qn(H)
QnPH
SD529
Current scan time
(in 100 s units)
SD532
Minimum scan
time for low
speed execution
type programs
Minimum scan
time (in 1 ms
units)
Stores the minimum value of the scan time of a low speed execution
type program into SD532 and SD533.
(Measurement is made in 100 s units.)
SD532: Stores the ms place. (Storage range: 0 to 65535)
SD533: Stores the s place. (Storage range: 0 to 900)
S (Every END
processing)
New
SD533
Minimum scan
time (in 100 s
units)
SD534
Maximum scan
time for low
speed execution
type programs
Maximum scan
time (in 1 ms
units)
Stores the maximum value of the scan time except that of the first scan
of a low speed execution type program into SD534 and SD535.
(Measurement is made in 100 s units.)
SD534: Stores the ms place. (Storage range: 0 to 65535)
SD535: Stores the s place. (Storage range: 0 to 900)
S (Every END
processing)
New
SD535
Maximum scan
time (in 100 s
units)
SD540
END processing
time
END processing
time (in 1 ms
units)
Stores the time from the end of a scan execution type program to the
start of the next scan into SD540 and SD541.
(Measurement is made in 100 s units.(For the Universal model QCPU,
in 1 s units.))
SD540: Stores the ms place. (Storage range: 0 to 65535)
SD541: Stores the s place. (Storage range: 0 to 900) (Storage range: 0
to 900 (For the Universal model QCPU, storage range is 0 to 999))
S (Every END
processing)
New
Qn(H)
QnPH
QnPRH
QnU
SD541
END processing
time (in 100 s
units)