Mitsubishi Electronics QnUCPU Home Theater Server User Manual


 
App - 12
Appendix 3.1.2 Replacing High Performance model QCPU with Universal
model QCPU
(1) System configuration
*1: The serial number (first five digits) of the applicable module (Q02UCPU, Q03UDCPU, Q04UDHCPU, Q06UDHCPU, Q13UDHCPU, and
Q26UDHCPU) must be "10041" or earlier.
TableApp.9 Precautions for replacement and replacement methods (System configuration)
Item Precautions Replacement method Reference
Use of AnS/A series
module
AnS/A series modules are not supported. Use Q series modules. ---
GOT GOT900 series cannot be connected. Use GOT1000 series. ---
Programming tool
connection
Applicable USB cables are different.
• High Performance model QCPU
... A-B type
• Universal model QCPU
... A-miniB type
Use USB cables of A-miniB type. Or, use
USB conversion adapters of B-miniB
type.
---
Applicable products
and software
Products and softwares compatible with
the Universal model QCPU must be used.
Products need to be replaced for the
compatibility with the Universal model
QCPU and software need to be upgraded
for the communication with the Universal
model QCPU are described in Appendix
3.2.
Appendix 3.2
Multiple CPU system
To configure a multiple CPU system, CPU
modules compatible with the Universal
model QCPU must be used.
CPU modules compatible with the
Universal model QCPU are described in
Appendix 3.2.
Appendix 3.2
In a multiple CPU system using the
Motion CPU, an existing auto refresh area
and user setting area cannot be used for
data communication with the Motion CPU.
For data communication with the Motion
CPU, use an auto refresh area and user
setting area in the multiple CPU high-
speed transmission area.
Chapter 4 in the QCPU
User's Manual (Multiple
CPU System)
Redundant power
supply system
*1
In a redundant power supply system
using the Q38RB redundant power supply
main base unit and the Q68RB redundant
power supply extension base unit, the
status of the power supply module cannot
be stored in the special relay and special
register (SM1780 to SM1783/SD1780 to
SD1783). The status cannot be displayed
on the system monitor screen.
Check the status of the power supply
module by the LED on the front of the
module.
Section 5.3 in the
QCPU User's Manual
(Hardware Design,
Maintenance and
Inspection)
MELSECNET/H
The simple dual-structured network
function is not supported.
---
Section 7.7 in the Q
Corresponding
MELSECNET/H
Network System
Reference Manual (PLC
to PLC network)