Mitsubishi Electronics QnUCPU Home Theater Server User Manual


 
8 - 14
Table8.10 I/O assignment setting list (continued)
Item
Parameter
No.
Description Setting range Default Reference
Switch setting 0407
H
Set various switches of an
intelligent function module.
Refer to the manual for the
intelligent function module used.
Blank Section 6.10
Detailed
setting
Error time
output mode
0403
H
Set whether to clear or hold the
output in case of a stop error in
the control CPU.
Clear/Hold Clear Section 6.8
H/W error
time PLC
operarion
mode
4004
H
Set whether to stop or continue
the operarion of the control
CPU in case of a hardware
failure of the intelligent function
module.
Stop/Continue Stop Section 6.9
I/O response
time
0405
H
Set a response time for the
input module, high-speed input
module, I/O combined module,
or interrupt module.
Input or I/O mix: 1ms, 5ms,
10ms, 20ms, or 70ms
Hi input or Interrupt: 0.1ms,
0.2ms, 0.4ms, 0.6ms, or 1ms
Input or I/O mix:
10ms
Hi input or Interrupt:
0.2ms
Section 6.7
Control PLC 0406
H
Set the control CPU for the input/
output modules and intelligent
function module.
No.1, No.2, No.3, or No.4 No.1
QCPU User's
Manual (Multiple