(3) System clocks/counters
Table12.4 Special relay
Number Name Meaning Explanation
Set by
(When Set)
Corres-
ponding
ACPU
M9
Corresponding
CPU
SM400 Always ON Normally is ON
S (Every END
processing)
M9036
QCPU
SM401 Always OFF Normally is OFF
S (Every END
processing)
M9037
SM402
After RUN, ON for 1
scan only
After RUN, ON for 1 scan only.
This connection can be used for scan execution type
programs only.
When an initial execution type program is used, this
relay turns OFF at the END processing of the scan
execution type program in the first scan after RUN.
S (Every END
processing)
M9038
Qn(H)
QnPH
QnPRH
QnU
After RUN, ON for 1 scan only.
S (Every END
processing)
New Q00J/Q00/Q01
SM403
After RUN, OFF for 1
scan only
After RUN, OFF for 1 scan only.
This connection can be used for scan execution type
programs only.
When an initial execution type program is used, this
relay turns OFF at the END processing of the scan
execution type program in the first scan after RUN.
S (Every END
processing)
M9039
Qn(H)
QnPH
QnPRH
QnU
After RUN, OFF for 1 scan only.
S (Every END
processing)
New Q00J/Q00/Q01
SM404
Low speed execution
type programON for 1
scan only after RUN
After RUN, ON for 1 scan only.
This connection can be used for low speed execution type
programs only.
S (Every END
processing)
New
Qn(H)
QnPH
SM405
Low speed execution
type programAfter
RUN, OFF for 1 scan
only
After RUN, OFF for 1 scan only.
This connection can be used for low speed execution type
programs only.
S (Every END
processing)
New
SM409 0.01 second clock
Repeatedly changes between ON and OFF at 5-ms
interval.
When Programmable Controller power supply is
turned ON or a CPU module reset is performed,
goes from OFF to start.
(Note that the ON-OFF status changes when the
designated time has elapsed during the execution of
the program.)
S (Status change) New
Qn(H)
QnPH
QnPRH
QnU
SM410 0.1 second clock
Repeatedly changes between ON and OFF at each
designated time interval.
When Programmable Controller power supply is
turned ON or a CPU module reset is performed,
goes from OFF to start.
(Note that the ON-OFF status changes when the
designated time has elapsed during the execution of
the program.)
S (Status change)
M9030
QCPU
SM411 0.2 second clock M9031
SM412 1 second clock M9032
SM413 2 second clock M9033
SM414 2n second clock
This relay alternates between ON and OFF at
intervals of the time (unit: s) specified in SD414.
When Programmable Controller power supply is
turned ON or a CPU module reset is performed,
goes from OFF to start.
(Note that the ON-OFF status changes when the
designated time has elapsed during the execution of
the program.)
S (Status change)
M9034form
at change
ON
OFF
ON
OFF
ON
OFF
1 scan
ON
OFF
1 scan of scan
execution type
program
Initial
execution
type program
ON
OFF
1 scan
ON
OFF
1 scan of scan
execution type
program
Initial
execution
type program
ON
OFF
1 scan
ON
OFF
1 scan
0.005s
0.005s
0.05s
0.05s
0.1s
0.1s
0.5s
0.5s
1s
1s
ns
ns