Table8.2 PLC system setting list (continued)
Item
Parameter
No.
Description Setting range Default Reference
Common pointer No. 1005
H Set the start number of common pointers. P0 to 4095 Blank Section 9.10.2
Points occupied by
empty slot
1007
H
Set the number of points for empty slots
on the main/extension base units.
0, 16, 32, 64, 128, 256, 512, or
1024 points
16 points Section 3.2.2
System
interrupt
settings
Fixed scan
interval (n:
28 to 31)
1008
H
Set each execution interval for the
interrupt pointers (I28 to I31).
0.5ms to 1000ms
(in increments of 0.5ms)
I28: 100.0ms
I29: 40.0ms
I30: 20.0ms
I31: 10.0ms
Section 9.11
Interrupt program/Fixed
scan program setting
1008
H
Enable or disable high speed execution
of interrupt programs or fixed scan
execution type programs.
Selected/deselected Deselected
Section 2.2.3,
2.3.4
Service processing
setting
1013
H
Select any of the following options.
Execute the process as the scan time
proceeds.
Specify service process time.
Specify service process execution
counts.
Execute it while waiting for constant
scan time setting.
• 1 to 99% (in increments of
1%)
1 to 10 (in increments of 1
time)
0.2 to 1000ms (in increments
of 0.1ms)
•Blank
Execute the
process as the
scan time
proceeds.: 10%
Section 6.24.1
PLC module change
setting (PLC module
change setting)
1017
H
Set items required when performing the
CPU module change with memory card
function.
Backup start setup contact
Backup start contact
Backup target data
Title setting
Blank Section 6.30