8 - 4
Table8.2 PLC system setting list (continued)
Item
Parameter
No.
Description Setting range Default Reference
Common pointer No. 1005
H Set the start number of common pointers. P0 to 4095 Blank Section 9.10.2
Points occupied by
empty slot
1007
H
Set the number of points for empty slots
on the main/extension base units.
0, 16, 32, 64, 128, 256, 512, or
1024 points
16 points Section 3.2.2
System
interrupt
settings
Fixed scan
interval (n:
28 to 31)
1008
H
Set each execution interval for the
interrupt pointers (I28 to I31).
0.5ms to 1000ms
(in increments of 0.5ms)
• I28: 100.0ms
• I29: 40.0ms
• I30: 20.0ms
• I31: 10.0ms
Section 9.11
Interrupt program/Fixed
scan program setting
1008
H
Enable or disable high speed execution
of interrupt programs or fixed scan
execution type programs.
Selected/deselected Deselected
Section 2.2.3,
2.3.4
Service processing
setting
1013
H
Select any of the following options.
• Execute the process as the scan time
proceeds.
• Specify service process time.
• Specify service process execution
counts.
• Execute it while waiting for constant
scan time setting.
• 1 to 99% (in increments of
1%)
• 1 to 10 (in increments of 1
time)
• 0.2 to 1000ms (in increments
of 0.1ms)
•Blank
Execute the
process as the
scan time
proceeds.: 10%
Section 6.24.1
PLC module change
setting (PLC module
change setting)
1017
H
Set items required when performing the
CPU module change with memory card
function.
• Backup start setup contact
• Backup start contact
• Backup target data
• Title setting
Blank Section 6.30