6.32 Module error collection
6 - 165
(7) Clearing module error history
Clear module error history by clicking the in the Error History screen.
Note that error information on each intelligent function module displayed in the Module's Detailed Information
screen is not cleared.
The module error history is cleared when the standard RAM is formatted.
Note that a module error collection file cannot be deleted since it is automatically created after the CPU module is powered
off and then on or is reset. To delete the file, clear the setting and then format the standard RAM.
(8) Precautions
(a) Using the CPU module change function with memory card
Backing up or restoring data will stop collecting module errors.
Figure 6.128 Module's Detailed Information screen
Clear History
Error information displayed
here is not cleared.