Installation
4.5.1 Installation - X-STREAM XEGC, X-STREAM XEGP
Fig. 4-13: Conguration of XSTI Terminal Adapter
A XSTI adapter can optionally be used to con-
nect analog IN cables to screw-type terminals
instead of a submin-D plugs and sockets. The
adapter is plugged onto the unit´s submin-D
connector X5.
Analog Inputs
Pin Signal
P3.1 not used
P3.2 not used
P3.3 not used
P3.4 not used
P3.5 not used
P3.6 not used
P3.7 not used
P3.8 not used
P3.9 not used
P3.10 not used
P3.11 not used
P3.12 not used
P2.1 BR 1 t a wire bridge here to apply analog
P2.2 BR 1 signal in current mode to input 1
P2.3 Input 1 high (+)
P2.4 Input 1 high (+)
P2.5 Input 1 low (-)
P2.6 Input 1 low (-)
P2.7 BR 2 t a wire bridge here to apply analog
P2.8 BR 2 signal in current mode to input 2
P2.9 Input 2 high (+)
P2.10 Input 2 high (+)
P2.11 Input 2 low (-)
P2.12 Input 2 low (-)
{
}
{
}
IN1
Mode
IN2
Mode
1 Connector for socket X5 (on reverse side)
2 Screw-type terminals
3 Reserved for future use
1 2
3
Recommended
wire gauge:
0.14 ... 1.5 mm
2
(AWG 26 ... AWG 16)
end sleeves not re-
quired
Skinning length: 5 mm (0.2")
Thread: M2
Min. tightening
torque:
0.25 Nm
(2.21 in.lb)