Emerson HASXEE-IM-HS TV Video Accessories User Manual


 
Emerson Process Management GmbH & Co. OHG 9-19
X-STREAM XE
Instruction Manual
HASXEE-IM-HS
04/2010
9
Modbus Commands
9.3 List of Parameters and Registers - Sorted by Tag Name
Tag Name Address
Data
Type
Client
Access
Description
Modicon Daniel
Setup.In/Outputs.AO.AdjustEnd4
6391…
6392
9196 Float R/W
ne adjustment for end range of out-
put4
Setup.In/Outputs.AO.AdjustEnd5
6399…
6400
9200 Float R/W
ne adjustment for end range of out-
put5
Setup.In/Outputs.AO.AdjustStart1
6365…
6366
9183 Float R/W
ne adjustment for start range of
output1
Setup.In/Outputs.AO.AdjustStart2
6373…
6374
9187 Float R/W
ne adjustment for start range of
output2
Setup.In/Outputs.AO.AdjustStart3
6381…
6382
9191 Float R/W
ne adjustment for start range of
output3
Setup.In/Outputs.AO.AdjustStart4
6389…
6390
9195 Float R/W
ne adjustment for start range of
output4
Setup.In/Outputs.AO.AdjustStart5
6397…
6398
9199 Float R/W
ne adjustment for start range of
output5
Setup.In/Outputs.AO.AutoScale1 3273 3273 Word R/W
Auto scale for ranged signals on out-
put1 (0=NO, 1=Yes)
Setup.In/Outputs.AO.AutoScale2 3278 3278 Word R/W
Auto scale for ranged signals on out-
put2 (0=NO, 1=Yes)
Setup.In/Outputs.AO.AutoScale3 3283 3283 Word R/W
Auto scale for ranged signals on out-
put3 (0=NO, 1=Yes)
Setup.In/Outputs.AO.AutoScale4 3288 3288 Word R/W
Auto scale for ranged signals on out-
put4 (0=NO, 1=Yes)
Setup.In/Outputs.AO.AutoScale5 3293 3293 Word R/W
Auto scale for ranged signals on out-
put5 (0=NO, 1=Yes)
Setup.In/Outputs.AO.EndRange1
6363…
6364
9182 Float R/W
level where analoge output scaling
ends on output1
Setup.In/Outputs.AO.EndRange2
6371…
6372
9186 Float R/W
level where analoge output scaling
ends on output2
Setup.In/Outputs.AO.EndRange3
6379…
6380
9190 Float R/W
level where analoge output scaling
ends on output3
Setup.In/Outputs.AO.EndRange4
6387…
6388
9194 Float R/W
level where analoge output scaling
ends on output4
Setup.In/Outputs.AO.EndRange5
6395…
6396
9198 Float R/W
level where analoge output scaling
ends on output5
Setup.In/Outputs.AO.FailMode1 3274 3274 Word R/W
Behavior on errors output1 (0=Track,
1=-10%Start, 2=+10%End)
Setup.In/Outputs.AO.FailMode2 3279 3279 Word R/W
Behavior on errors output2 (0=Track,
1=-10%Start, 2=+10%End)
Setup.In/Outputs.AO.FailMode3 3284 3284 Word R/W
Behavior on errors output3 (0=Track,
1=-10%Start, 2=+10%End)
Setup.In/Outputs.AO.FailMode4 3289 3289 Word R/W
Behavior on errors output4 (0=Track,
1=-10%Start, 2=+10%End)
Setup.In/Outputs.AO.FailMode5 3294 3294 Word R/W
Behavior on errors output5 (0=Track,
1=-10%Start, 2=+10%End)
Setup.In/Outputs.AO.Hold1 3275 3275 Word R/W
Hold output1 on calibrations (0=Track,
1=Hold)