9.3 List of Parameters and Registers - Sorted by Tag Name
Tag Name Address
Data
Type
Client
Access
Description
Modicon Daniel
Setup.In/Outputs.AO.Hold2 3280 3280 Word R/W
Hold output2 on calibrations (0=Track,
1=Hold)
Setup.In/Outputs.AO.Hold3 3285 3285 Word R/W
Hold output3 on calibrations (0=Track,
1=Hold)
Setup.In/Outputs.AO.Hold4 3290 3290 Word R/W
Hold output4 on calibrations (0=Track,
1=Hold)
Setup.In/Outputs.AO.Hold5 3295 3295 Word R/W
Hold output5 on calibrations (0=Track,
1=Hold)
Setup.In/Outputs.AO.NumberOuts 3270 3270 Word R/W number of analog outputs
Setup.In/Outputs.AO.OutRange1 3272 3272 Word R/W
range of output1 (0=0..20mA, 1=4-
20mA)
Setup.In/Outputs.AO.OutRange2 3277 3277 Word R/W
range of output2 (0=0..20mA, 1=4-
20mA)
Setup.In/Outputs.AO.OutRange3 3282 3282 Word R/W
range of output3 (0=0..20mA, 1=4-
20mA)
Setup.In/Outputs.AO.OutRange4 3287 3287 Word R/W
range of output4 (0=0..20mA, 1=4-
20mA)
Setup.In/Outputs.AO.OutRange5 3292 3292 Word R/W
range of output5 (0=0..20mA, 1=4-
20mA)
Setup.In/Outputs.AO.SignalAsgn1 3271 3271 Word R/W assigned signal output1
Setup.In/Outputs.AO.SignalAsgn2 3276 3276 Word R/W assigned signal output2
Setup.In/Outputs.AO.SignalAsgn3 3281 3281 Word R/W assigned signal output3
Setup.In/Outputs.AO.SignalAsgn4 3286 3286 Word R/W assigned signal output4
Setup.In/Outputs.AO.SignalAsgn5 3291 3291 Word R/W assigned signal output5
Setup.In/Outputs.AO.StartRange1
6361…
6362
9181 Float R/W
level where analoge output scaling
starts on output1
Setup.In/Outputs.AO.StartRange2
6369…
6370
9185 Float R/W
level where analoge output scaling
starts on output2
Setup.In/Outputs.AO.StartRange3
6377…
6378
9189 Float R/W
level where analoge output scaling
starts on output3
Setup.In/Outputs.AO.StartRange4
6385…
6386
9193 Float R/W
level where analoge output scaling
starts on output4
Setup.In/Outputs.AO.StartRange5
6393…
6394
9197 Float R/W
level where analoge output scaling
starts on output5
Setup.In/Outputs.DI.Node_DI1 3221 3221 Word R/W node of DigInp1 / XDIO1 Inp1
Setup.In/Outputs.DI.Node_DI10 3238 3238 Word R/W node of DigInp10 / XDIO2 Inp3
Setup.In/Outputs.DI.Node_DI11 3239 3239 Word R/W node of DigInp11 / XDIO2 Inp4
Setup.In/Outputs.DI.Node_DI12 3240 3240 Word R/W node of DigInp12 / XDIO2 Inp5
Setup.In/Outputs.DI.Node_DI13 3241 3241 Word R/W node of DigInp13 / XDIO2 Inp6
Setup.In/Outputs.DI.Node_DI14 3242 3242 Word R/W node of DigInp14 / XDIO2 Inp7
Setup.In/Outputs.DI.Node_DI2 3222 3222 Word R/W node of DigInp2 / XDIO1 Inp2
Setup.In/Outputs.DI.Node_DI3 3223 3223 Word R/W node of DigInp3 / XDIO1 Inp3
Setup.In/Outputs.DI.Node_DI4 3224 3224 Word R/W node of DigInp4 / XDIO1 Inp4
Setup.In/Outputs.DI.Node_DI5 3225 3225 Word R/W node of DigInp5 / XDIO1 Inp5
Setup.In/Outputs.DI.Node_DI6 3226 3226 Word R/W node of DigInp6 / XDIO1 Inp6
Setup.In/Outputs.DI.Node_DI7 3227 3227 Word R/W node of DigInp7 / XDIO1 Inp7