Emerson Process Management GmbH & Co. OHG 9-5
X-STREAM XE
Instruction Manual
HASXEE-IM-HS
04/2010
9
Modbus Commands
9.3 List of Parameters and Registers - Sorted by Tag Name
Tag Name Address
Data
Type
Client
Access
Description
Modicon Daniel
Control.Calibration.Zero_5 2005 2005 Boolean R/W Zero calibration comp5 (1=start)
Control.Calibration.Zero_All 2021 2021 Boolean R/W Zero calibration all (1=start)
Control.Calibration.ZeroSpan_1 2011 2011 Boolean R/W Zero+span calibration comp1 (1=start)
Control.Calibration.ZeroSpan_2 2012 2012 Boolean R/W Zero+span calibration comp1 (1=start)
Control.Calibration.ZeroSpan_3 2013 2013 Boolean R/W Zero+span calibration comp1 (1=start)
Control.Calibration.ZeroSpan_4 2014 2014 Boolean R/W Zero+span calibration comp1 (1=start)
Control.Calibration.ZeroSpan_5 2015 2015 Boolean R/W Zero+span calibration comp1 (1=start)
Control.Calibration.ZeroSpan_All 2023 2023 Boolean R/W Zero+span calibration all (1=start)
Info.ProgramVersion
4011…
4016
4011…
4016
String RO software release version
Info.SensorVersion 4026 4026 Word RO Version number of sensor rmware
Info.SerialNumber
3141…
3147
3141…
3147
String RO serial number of the device
PV1
6001…
6002
9001 Float RO Primary Variable 1
PV2
6003…
6004
9002 Float RO Primary Variable 2
PV3
6005…
6006
9003 Float RO Primary Variable 3
PV4
6007…
6008
9004 Float RO Primary Variable 4
PV5
6009…
6010
9005 Float RO Primary Variable 5
Service.General.ChannelActive1 3001 3001 Word R/W built-in component1
Service.General.ChannelActive2 3002 3002 Word R/W built-in component2
Service.General.ChannelActive3 3003 3003 Word R/W built-in component3
Service.General.ChannelActive4 3004
3004 Word R/W built-in component4
Service.General.ChannelActive5 3005 3005 Word R/W built-in component5
Service.General.Identication.CPLDVersion 4028 4028 Word RO Version number of CPLD rmware
Service.General.Identication.Manufacturin-
gInfo
3251…
3266
3251…
3266
String RO
Infos stored for manufacturing purpo-
ses
Service.General.Identication.ProgramVer-
sionDate
4017…
4022
4017…
4022
String RO software release date
Service.General.Identication.SensorBuild 4027 4027 Word RO Build number of sensor rmware
Service.Measurement.AbsMaxRange1
6323…
6324
9162 Float R/W absolute maximum range of comp1
Service.Measurement.AbsMaxRange2
6327…
6328
9164 Float R/W absolute maximum range of comp2
Service.Measurement.AbsMaxRange3
6331…
6332
9166 Float R/W absolute maximum range of comp3
Service.Measurement.AbsMaxRange4
6335…
6336
9168 Float R/W absolute maximum range of comp4
Service.Measurement.AbsMaxRange5
6339…
6340
9170 Float R/W absolute maximum range of comp5
Service.Measurement.AbsMinRange1
6321…
6322
9161 Float R/W absolute minimum range of comp1