Modbus Commands
9.3 List of Parameters and Registers - Sorted by Tag Name
Tag Name Address
Data
Type
Client
Access
Description
Modicon Daniel
Control.Calibration.Zero_5 2005 2005 Boolean R/W Zero calibration comp5 (1=start)
Control.Calibration.Zero_All 2021 2021 Boolean R/W Zero calibration all (1=start)
Control.Calibration.ZeroSpan_1 2011 2011 Boolean R/W Zero+span calibration comp1 (1=start)
Control.Calibration.ZeroSpan_2 2012 2012 Boolean R/W Zero+span calibration comp1 (1=start)
Control.Calibration.ZeroSpan_3 2013 2013 Boolean R/W Zero+span calibration comp1 (1=start)
Control.Calibration.ZeroSpan_4 2014 2014 Boolean R/W Zero+span calibration comp1 (1=start)
Control.Calibration.ZeroSpan_5 2015 2015 Boolean R/W Zero+span calibration comp1 (1=start)
Control.Calibration.ZeroSpan_All 2023 2023 Boolean R/W Zero+span calibration all (1=start)
Info.ProgramVersion
4011…
4016
4011…
4016
String RO software release version
Info.SensorVersion 4026 4026 Word RO Version number of sensor rmware
Info.SerialNumber
3141…
3147
3141…
3147
String RO serial number of the device
PV1
6001…
6002
9001 Float RO Primary Variable 1
PV2
6003…
6004
9002 Float RO Primary Variable 2
PV3
6005…
6006
9003 Float RO Primary Variable 3
PV4
6007…
6008
9004 Float RO Primary Variable 4
PV5
6009…
6010
9005 Float RO Primary Variable 5
Service.General.ChannelActive1 3001 3001 Word R/W built-in component1
Service.General.ChannelActive2 3002 3002 Word R/W built-in component2
Service.General.ChannelActive3 3003 3003 Word R/W built-in component3
Service.General.ChannelActive4 3004
3004 Word R/W built-in component4
Service.General.ChannelActive5 3005 3005 Word R/W built-in component5
Service.General.Identication.CPLDVersion 4028 4028 Word RO Version number of CPLD rmware
Service.General.Identication.Manufacturin-
gInfo
3251…
3266
3251…
3266
String RO
Infos stored for manufacturing purpo-
ses
Service.General.Identication.ProgramVer-
sionDate
4017…
4022
4017…
4022
String RO software release date
Service.General.Identication.SensorBuild 4027 4027 Word RO Build number of sensor rmware
Service.Measurement.AbsMaxRange1
6323…
6324
9162 Float R/W absolute maximum range of comp1
Service.Measurement.AbsMaxRange2
6327…
6328
9164 Float R/W absolute maximum range of comp2
Service.Measurement.AbsMaxRange3
6331…
6332
9166 Float R/W absolute maximum range of comp3
Service.Measurement.AbsMaxRange4
6335…
6336
9168 Float R/W absolute maximum range of comp4
Service.Measurement.AbsMaxRange5
6339…
6340
9170 Float R/W absolute maximum range of comp5
Service.Measurement.AbsMinRange1
6321…
6322
9161 Float R/W absolute minimum range of comp1