Programming Function Blocks and Features
Video Recorder – User Manual 133
Advanced Splitter Output (ADV SPLITTER)
This function can be used for heat/cool applications. It splits an input into 3 independently scaled
outputs: CVn_A1, CVn_A2 and CVn_A3 (Figure 4-12). For each output, when the input is between IN
LO LIM and IN HI LIM, the output is scaled between the OUT LO LIM and OUT HI LIM. Each output
holds its OUT LO LIM value when the input < the IN LO LIM value for that output. Each output holds its
OUT HI LIM value when the input > the IN HI LIM value for that output. Output limits (OUT LO LIM &
OUT HI LIM) cannot exceed 100% but can be negatively sloped (OUT HI LIM < OUT LO LIM).
A1 A2 A3
0 306090100
100
0
INPUT SOURCE VALUE (%)
OUTPUT
VALUE
(%)
Figure 4-12 Advanced Splitter (Default Outputs)
SPLIT
LOOP
AO
FEEDBACK
BC
A1
OV
AO
AO
BC
A2
BC
INPUT
SPLITTER
CV
FEEDBACK #1
FEEDBACK#2
Figure 4-13 Heat/Cool Configuration
Table 4-41 describes the Advanced Splitter prompts. See Table 4-2 for additional prompts.