Table 3-4 Function Block Parameter Designators (continued)
Function
Block
Type
Function Block
Name
Output
code
Parameter Name Parameter
Type
SP Setpoint Profiler OV
A1
PV
SN
SH
SE
SA
SI
SR
E1
thru
E9
EA
EB
thru
EG
Output Value
Auxiliary Output Value
Process Variable (Guaranteed Soak PV #1)
Segment Number
Hold Status
End Status
Active Status
Active or Hold Status
Ready Status
Event#1 Output
thru
Event#9 Output
Event#10 Output
Event#11 Output
thru
Event#16 Output
Analog
Analog
Analog
Analog
Discrete
Discrete
Discrete
Discrete
Discrete
Discrete
$
Discrete
AL Alarm PV
S2
OS
Process Variable (alarm’s input)
Compare Point (of Deviation alarm)
Output Status
Analog
Analog
Discrete
CN Constant OV
PV
Output Value
Process Variable (Constant’s input)
Analog
Analog
CV Calculated Value* OV
PV**
A(n)
BC
S2
D(n)
OS
Output Value
Process Variable
Analog Output #n
Back Calculation
Auxiliary input (link to totalizer preset)
Discrete Output
Output Status
Analog
Analog
Analog
Analog
Analog
Discrete
Discrete
*CV output codes are available for programming only if the CV has been programmed. For example, you
cannot program an input parameter with CV1 OV unless CV1 has been programmed.
**Input to the following CV types: Peak Pick, 1 Point Block Avg., 1 Point Rolling Avg., Scaling, Signal Select
TL Totalizer OV
PV
OS
S2
Output Value
Process Variable (Totalizer’s input)
Output Status
Preset Value
Analog
Analog
Discrete
Analog