Honeywell VRX180 DVR User Manual


 
Setpoint Profiler
Video Recorder – User Manual 195
Table 5-5 Edit Profile Prompts (continued)
Prompt Range/Selections Definition
TIME MULTIPLIER Number
Time Multiplier determines the speed at which
the profiler will run when in Fast Forward mode.
It is used for testing the profiler’s execution.
See Fast Forward.
When FAST FORWARD is ON(1), the profiler
will run at a speed determined by the TIME
MULTIPLIER parameter.
Example
The instrument is running at a 500msec scan
rate. The TIME MULTIPLIER is set to 60.
Therefore the profiler will run in (500msec x 60)
or 30 second increments.
Running a profiler in FAST FORWARD is a way
to check for proper functioning of the profiler’s
events and outputs, without having to wait for
the profiler to execute at its normal speed.
See Figure 5-11.