Video recorder – User Manual 8
Table 1-3 Analog Input --Non-linear types
Thermocouples -ITS-90 except where noted
Accuracy (1) Operating span
Min value
Reference range (2)
Type
°F °C
% Range
°F °C °F °C
J 0 to 2190 -18 to 1199 0.1 0.4 0.2
K 0 to 2500 -18 to 1371 0.1 0.4 0.2
E -450 to 1830 -268 to 999 0.1 0.4 0.2
T -300 to 752 -184 to 400 0.1 0.4 0.2
N 0 to 2372 -18 to 1300 0.1 0.6 0.3
B 110 to 3300 43 to 1816 0.1 2.5 1.4 752 to 3300 400 to 1816
R 0 to 3210 -18 to 1766 0.1 1.5 0.8
S 0 to 3210 -18 to 1766 0.1 1.6 0.9
W5/W26 (3)
0 to 4200 -18 to 2316 0.1 0.9 0.5 32 to 3272 0 to 1800
PLAT II (3)
-100 to 2500 -73 to 1371 0.1 0.4 0.2
NI-NIMO 32 to 2502 0 to 1372 0.1 0.4 0.2
RTD (4)
CU10 -100 to 310 -73 to 154
0.5 2.5 1.4
PT100 IEC -300 to 1570 -184 to 854 0.1 0.5 0.3
Pyrometry (Rayotube & Spectray) Types
Accuracy ( 5 )
Operating span
Max value Min value
Type
°F °C
°F °C °F °C
18890-0035 1200 to 2600 649 to 1426 4 2 1 0.6
18890-0073 800 to 1800 427 to 982 12.5 7 1 0.6
18890-0074 1100 to 2300 594 to 1260 3 1.7 1 0.6
18890-0075 1500 to 3300 816 to 1815 6 3 1.8 1
18890-0163 200 to 1000 94 to 537 11 6 1.5 0.8
18890-0216 2110 to 4600 1155 to 2537 8 4.4 1.8 1
18890-0412 1375 to 3000 747 to 1648 10 5.6 1.3 0.7
18890-00643 1850 to 4000 1010 to 2204 8 4.4 1 0.6
18890-1729 1650 to 3600 899 to 1982 5 3 1.5 0.8
18890-3302 750 to 1600 399 to 871 6 3 1 0.6
18890-5423 2210 to 5000 1210 to 2760 18 10 2 1.1
18894-0579 752 to 2552 400 to 1400 33 18 3.6 2
18899-8814 340 to 1800 172 to 982 11 6 2 1.1
18894-9014 752 to 2552 400 to 1400 20 11 2.6 1.4
Spectray 18885 1832 to 3452 1000 to 1900 30 17 0.6 0.3
Spectray 18885-1 1292 to 2912 700 to 1600 60 33 0.6 0.3
Spectray 18885-2 806 to 1400 430 to 760 38 21 0.2 0.1
Spectray 18886 1833 to 3452 1001 to 1900 20 11 0.6 0.3
Spectray 18886-1 1292 to 2912 700 to 1600 80 44 0.6 0.3
18874-0578 752 to 2552 400 to 1400 3.6 2 1.8 1
18875-0579 752 to 2552 400 to 1400 3.6 2 1.8 1
NOTES:
1: The accuracy will be the larger value between Min Value and %range of the selected limits
2: Reference range = operating range when blank
3: IPTS-68
4: T° influence: 0.5% per 10°C on Cu 10 ohms, 0.3% per 10°C on Pt 100 200°C
5: For Pyrometry, the worst accuracy (Max value) is at the low range limit , the best (Min value) is at the high limit.
- For non linear temperature transmitter, the transmitter range MUST be identical to the input range of the recorder.