Honeywell VRX180 DVR User Manual


 
Setpoint Profiler
Video Recorder – User Manual 189
Parameter name Definition Triggered
by
Conditions
present
Result
GUARANTEED
SOAK
See Guaranteed Soak on page 182. Level ON Excessive
deviation
between
profiler and
PV #1 or PV
#2 & the
segment’s
GUAR SOAK
#1 or GUAR
SOAK #2 is
enabled.
Profiler is
put on Hold
HOLD
LEVEL/EDGE
EDIT Grants access to the profile’s segments
edition page, see table 5-5.
5.4 How to set up a profiler
Up to 4 profilers can be programmed, depending on the options on your instrument. There are two
menus for programming a profiler: PROGRAM PROFILERS in the Program menu, and SETPOINT
PROFILES in the Online menu. Both must be accessed to program a profiler. Both menus are
described in this section.
Program Profilers menu (in Program mode)
This menu lets you define various parameters for controlling the profiler’s execution. To access the
Program Profilers menu:
1. Press the Menu button until a main menu is displayed.
2. Select Set Mode and change the mode to Program.
3. Select Program Profilers.
4. Select a profiler (#1 through #4) to program. Only profilers that are not actively running are
selectable.
Table 5-3 briefly describes the prompts for all profilers. For detailed descriptions, refer to Sections 5.2
and 5.3. See Table 4-2 for additional prompts.