Honeywell VRX180 DVR User Manual


 
Programming Function Blocks and Features
Video Recorder – User Manual 134
Table 4-41 Advanced Splitter Prompts
Prompt Range/Selections Definition
RANGE LOW
RANGE HIGH
OFF or number Enter the output's display limits. Output is not clamped or
flashed when it exceeds these limits.
INPUT OFF, analog parameter,
number
Input source. Typically, this is the output value (OV) of a
Split Output type of loop.
FEEDBACK #1 OFF, AOn BC, LPn BC Select the back calculation value (BC) of the analog output
assigned to the A1, A2, and A3 outputs, respectively.
FEEDBACK #2
FEEDBACK #3
OUT#1 IN LO LIM
OUT#1 IN HI LIM
OFF or number Enter a range for A1's input. Defauts are 0 for low limit & 30
for high limit. When input is between these values, A1
output is scaled between OUT#1 OUT LO LIM & OUT#2
OUT HI LIM.
OUT#1 OUT LO LIM
OUT#1 OUT HI LIM
OFF or number Enter OFF or a range for A1’s output. Defaults are 0 for low
limit & 100 for high limit. Scales A1 output.
OUT#2 IN LO LIM
OUT#2 IN HI LIM
OFF or number Enter a range for A2’s input. Defaults are 30 for low limit &
60 for high limit. When input is between these values, A2
output is scaled between OUT#2 OUT LO LIM & OUT#2
OUT HI LIM.
OUT#2 OUT LO LIM
OUT#2 OUT HI LIM
OFF or number Enter OFF or a range for A2’s output. Defaults are 0 for low
limit & 100 for high limit. Scales A2 output.
OUT#3 IN LO LIM
OUT#3 IN HI LIM
OFF or number Enter a range for A3’s input. Defaults are 60 for low limit &
90 for high limit. When input is between these values, A3
output is scaled between OUT#3 OUT LO LIM & OUT#3
OUT HI LIM.
OUT#3 OUT LO LIM
OUT#3 OUT HI LIM
OFF or number Enter OFF or a range for A3’s output. Defaults are 0 for low
limit & 100 for high limit. Scales A3 output.