Power MAP 3945: Power OFF not Possible in Local Mode
Symptom Explanation Conditions That Could Cause This Symptom
Power OFF is not possible in local
mode
The power control is not in local mode
Relay K1
Control Panel
PCC
Attention
Power may be present when nothing is dis-
played on the control panel.
001
When the power control is in local mode, a 3 is
displayed at the control panel.
Is the power control in local mode?
Yes No
002
Power the 3745 OFF as follows:
Set the power control to local mode:
Using Power Control, scroll till
the value is 3.
Press Validate.
Press Power Off.
Continue whit Step 003.
003
Is the 3745 still powered ON?
Yes No
004
Go to “CE Leaving Procedure” on
page 4-102.
005
Are the blowers stopped?
Yes No
006
Suspect relay K1 located in primary
power box 01H-A2.
Refer to the YZ pages for wiring.
Repair and re-initiate the command.
If correct, go to “CE Leaving Procedure”
on page 4-102.
007
Exchange the FRU group 37 on page 1-51. Go
to “3745 FRU Group Table” on page 1-49.
2-26 3745 Models 130 to 17A: MIP