CE leaving procedure
CE Leaving Procedure
The maintenance package has determined that the 3745 is ready to be returned to normal operation.
001
Did you work on the 3745 Model 17A?
Yes No
002
Go to Step 004.
003
In the MOSS-E View window, double click on the service processor icon.
The Service Processor Menu window is displayed.
Click on the Configuration Management option.
Double click on the Manage Remote Operations option.
In the Remote Operation Management window, select the Remote operations authorization option
and click on OK.
On the Remote Support Facility window, select the two following options:
Enable Remote Support Facility
Generate alerts
Click on OK.
Click on Cancel to return to Service Processor Menu.
Click on Function and Exit to return to the MOSS-E View window.
In the MOSS-E View window, click on Program in the action bar.
Click on Log Off MOSS-E.
Continue with Step 004.
004
You should use the following list to ensure that the machine is in suitable condition for customer operation
and that all call information is recorded.
1. Replace any cables removed.
2. Check the battery voltage and exchange it if necessary.
3. Do all the actions that apply in the following list:
If You Have What You Should Do
Exchanged all the FRUs that were
identified for an intermittent problem
or a problem not detected by the diag-
nostics (tentative repair which can be
unsuccessful).
Use the manual BER correlation (BRC, refer to the
IBM
3745 Service Functions
) to point out some additional
potentially failing FRUs.
1. Find, in the Error Log Display the alarm with the Ref-
erence Code that you used to exchange the FRUs.
2. Select the BER range which occurs in the same time
frame as the alarm.
3. Type BRC in the Menu 3.
4. Enter the most recent and the oldest BER in the
range you have selected.
5. Press SEND.
6. Note the extra FRUs, if any, provided by the BER cor-
relation and inform the HSC/HCS or update the PMH
in case of problem reoccurence.
Exchanged a Board If the new board has a different part number with regard
to the old one, you have to update the 'Board Level' label
located on the front door.
Exchanged a LIC Board Check the address plugging.