5-94
5.3 Serial Communication
5.3.10 CSET instruction (initial setting)
ZP_CSET
[ST]
IF(Var_Flag_Inst=TRUE)THEN
FMOVP(TRUE,0,112, Var_ControlData[0]); (* Resets D0 to D111 to 0 *)
MOVP(TRUE, 0, Var_ControlData[0]); (* Sets execution type *)
MOVP(TRUE, 1, Var_ControlData[2]); (* Sets request type *)
MOVP(TRUE, 1, Var_ControlData[3]); (* Sets word/byte unit to word *)
MOVP(TRUE, H400, Var_ControlData[4]); (* Sets on-demand start address *)
MOVP(TRUE, 0, Var_ControlData[5]); (* Sets on-demand buffer size *)
MOVP(TRUE,H0C00, Var_ControlData[6]); (* Sets send buffer start address *)
MOVP(TRUE, H400, Var_ControlData[7]); (* Sets send buffer size *)
MOVP(TRUE, H600, Var_ControlData[8]); (* Sets receive buffer start address *)
MOVP(TRUE, H200, Var_ControlData[9]); (* Sets receive buffer size *)
ZP_CSET(TRUE, "U0", 1, Var_ControlData, Var_Dummy, Var_Result);
(* Performs initialization *)
END_IF;
IF(Var_Result[0]=TRUE)THEN (* Execution finished *)
IF(Var_Result[1]=FALSE)THEN (* Normal completion *)
SET(TRUE, Var_Flag_Normal); (* Turns normal completion flag ON *)
ELSE (* Error completion *)
SET(TRUE, Var_Flag_Error); (* Turns error completion flag ON *)
END_IF;
END_IF;