5.4 Network Dedicated Instruction
5.4.10 WRITE instruction
5-157
J_WRITE, G_WRITE
5
MODULE DEDICATED
INSTRUCTION
J_WRITE, G_WRITE
Control Data
Device Item Setting data Setting range Setting side
[0]
Execution/Error completion
type
Execution type (bit 0)
0000H,
0001
H,
0080
H,
0081
H
User
Ethernet
0: Without arrival confirmation
When the target station is on the same network... Completed when
data are sent
from the host
station.
When the target station is on another network ..... Completed when
data reach to a
relay station on
the same
network.
1: With arrival confirmation
Completed when data are written to the target station.
MELSECNET/H CC-Link IE
0: Without arrival confirmation
• When the target station is on the same network
Completed when data are sent from the host station.
• When the target station is on another network
Completed when data reach to a relay station on the same
network.
1: With arrival confirmation
Completed when data are written to the target station.
When '0: Without arrival confirmation' is specified, even if writing to
the target station is completed abnormally in the following cases,
the processing of the instruction in the host station is completed
normally.
• Communication itself was completed normally, although the
sent data were erroneous.
• Data could not be written to the target station because
instructions from multiple stations were executed to the same
station. (An error code (F222
H, E006H, E205H, D202H, or
D282
H) is detected at the target station.)
s1
b15 b7 b0to to
0
0
2
1
Execution source
Target station
Completed
Execution source
Target station
Completed
Relay station
Execution source
Target station
Completed
Relay station
Completed
Target station
Completed
Target stationRequest source
Completed
Target station
Request source
Relay station
Completed
Target station
Request source
Relay station
Target station
Completed