Mitsubishi Electronics MELSEC Q series MELSEC L series Home Theater Server User Manual


 
5-214
5.4 Network Dedicated Instruction
5.4.24 CCPASET instruction
G_CCPASET
5.4.24 CCPASET instruction
G_CCPASET
*1: Local devices and file registers per program cannot be used as setting data.
Function
This instruction sets parameters for master/local module (master station).
G(P)_CCPASET
P: Executing condition
:
indicates any of the following
instructions.
G_CCPASET GP_CCPASET
Input argument EN:
Executing condition : Bit
Un*:
Start I/O number of the module
(00 to FE: Higher two digits when expressing the I/O number in
three digits)
: ANY16
s1:
Variable that stores control data : Array of ANY16 [0..3]
s2:
Start number of the host station's device that stores network
configuration setting data.
: Array of ANY16 [0..599]
s3:
Start number of the host station's device that stores reserved
station specification data.
: Array of ANY16 [0..7]
s4:
Start number of the host station's device that stores error
invalid station setting data.
: Array of ANY16 [0..7]
Output argument ENO:
Execution result : Bit
d:
Variable that turns ON upon completion of the instruction
d[1] also turns ON at the time of error completion.
: Array of Bit [0..1]
Setting
data
*1
Internal device
R, ZR
J\
U\G
Zn
Constant
Others
Bit Word Bit Word




CC IE F
Structured ladder/FBD
EN ENO
Un*
d
s1
s2
s3
s4
G_CCPASET
ST
G_CCPASET
(EN, Un*, s1, s2, s3, s4, d);
ENO:=
s1
s2
s3
s4
d