Mitsubishi Electronics MELSEC Q series MELSEC L series Home Theater Server User Manual


 
5-176
5.4 Network Dedicated Instruction
5.4.13 RECV instruction
J_RECV, G_RECV
Control Data
Device Item Setting data Setting range Setting side
[0]
Error completion type
Error completion type (bit 7)
Specify the clock data setup status at the time of error completion.
0: Clock data at the time of error completion is not set in the area
starting from [11].
1: Clock data at the time of error completion is set in the area starting
from [11].
0000H,
0080
H
User
[1]
Completion status
The instruction completion status is stored.
0 : Normal completion
Other than 0 : Error completion (error code)
System
[2]
Host station channel
Specify the channel of host station that stores receive data.
1 to 8 User
[3]
Channel used by sending
station
Channel used by the sending station is stored.
1 to 8: Channel
System
[4]
Network No. of sending
station
Network number of the sending station is stored.
1 to 239: Network number
System
[5]
Sending station No.
Station number of the sending station is stored.
System
[6]
(Reserved)
––
[7]
(Reserved)
––
[8]
Arrival monitoring time
Specify the monitoring time required for the instruction completion.
When the instruction is not completed within the monitoring time, it
completes abnormally.
0 to 32767 User
s
b15 b7 b0to to
0
0
s
s
s
s
Description Setting value
MELSECNET/H
Ethernet
CC-Link IE Controller Network
1 to 8
CC-Link IE Field Network 1 to 2
s
s
s
Setting value Description
MELSECNET/H 1 to 64
Ethernet
CC-Link IE Controller Network
1 to 120
CC-Link IE Field Network -
Master station 125 (7DH)
Local station or the intelligent device
station
1 to 120
s
s
s
Description Setting value
Ethernet
0 to TCP retransmission
timer value: Monitoring is
performed by the TCP
retransmission timer value.
(TCP retransmission timer
value + 1) to 16383:
Monitoring time (unit:
second)
0 to 16383
CC-Link IE
MELSECNET/H
0: 10 seconds
1 to 32767: 1 to 32767
seconds
0 to 32767