Mitsubishi Electronics MELSEC Q series MELSEC L series Home Theater Server User Manual


 
5.4 Network Dedicated Instruction
5.4.18 RRUN instruction
5-199
Z_RRUN_J, Z_RRUN_U
5
MODULE DEDICATED
INSTRUCTION
Z_RRUN_J,
Z_RRUN_U
5.4.18 RRUN instruction
Z_RRUN_J, Z_RRUN_U
Z(P)_RRUN_J
Z(P)_RRUN_U
P: Executing condition
:
indicates any of the following
instructions.
Z_RRUN_J ZP_RRUN_J
Z_RRUN_U ZP_RRUN_U
Input argument EN:
Executing condition :Bit
Jn*:
Network number of the target station (1 to 239, 254)
254: Network specified in
"Valid module during other station
access
"
:String
Un*:
Start I/O number of the host station network No.
(00 to FE: Higher two digits when expressing the I/O number in
three digits)
:String
s1:
Channel used by host station
For the RRUN instruction, specify the channel used by host
station that is the same as the one used for the RSTOP
instruction.
:ANY16
s2:
Target station number
(1) Station number specification
Host station is Universal model QCPU: 1 to 120
Host station is anything other than Universal model QCPU: 1
to 64
(2) Group specification
81
H to A0H: All stations of a group (No.1 to 32)
(3) All stations
FF
H: All stations of the target network No. (Except the host
station)
To specify a group or all stations, specify '0000
H' or '03FFH' for
the target station's CPU type (s3).
:ANY16
s3:
Target station's CPU type
0000
H: Target station CPU/control CPU/host system CPU
(Specified data are the same as '03FF
H'.)
03E0
H: Multi-CPU No. 1/
target station CPU (single CPU system)
03E1
H: Multi-CPU No. 2
03E2H: Multi-CPU No. 3
03E3
H: Multi-CPU No. 4
03FF
H: Target station CPU/control CPU/host system CPU
:ANY16
s4:
Mode :ANY16
Output argument ENO:
Execution result :Bit
d:
Variable that turns ON upon completion of the instruction
d[1] also turns ON at the time of error completion.
:Array of bit [0..1]
CC IE C
NET/H
Structured ladder/FBD
EN ENO
Jn*
d
s1
s2
s3
s4
Z_RRUN_J
EN ENO
Un*
d
s1
s2
s3
s4
Z_RRUN_U
ST
Z_RRUN_J
(EN, Jn*, s1, s2, s3, s4, d);
ENO:=
Z_RRUN_U
(EN, Un*, s1, s2, s3, s4, d);
ENO:=