5.4 Network Dedicated Instruction
5.4.23 REMTO instruction
5-213
Z_REMTO
5
MODULE DEDICATED
INSTRUCTION
Z_REMTO
Function
This instruction writes data to the buffer memory of an intelligent function module on the
intelligent device station/remote I/O station.
Program Example
The following program makes the A/D conversion enable setting on channels.
[Structured ladder/FBD]
[ST]
IF(Var_Flag_Inst=TRUE)THEN
MOV(TRUE,H8,D0);
(* A/D Conversion enable/disable setting *)
MOV(TRUE,50,D2);
(* CH2 time/count averaging setting *)
MOV(TRUE,1000,D3);
(* CH3 time/count averaging setting *)
MOV(TRUE,H604,D9);
(* Averaging processing specification *)
ZP_REMTO(TRUE,"J1",1,1,H2,H0,10,D0,Var_Result);
(* Writes data to buffer memory *)
END_IF;
IF((Var_Result[0]=TRUE) AND (Var_Result[1]=FALSE))THEN
SET(TRUE,Y1029);
(* Turns operating condition setting request (Y9) ON *)
END_IF;
IF((Y1029=TRUE) AND (X1029=FALSE))THEN
RST(TRUE,Y1029);
(* Turns operating condition setting request (Y9) OFF *)
END_IF;
A/D Conversion
enable/disable
setting
CH2 time/count
averaging setting
CH3 time/count
averaging setting
Averaging processing
specification
Writes data to
buffer memory
Turns operating
condition setting
request (Y9) ON
Turns operating
condition setting
request (Y9) OFF