5.1 Analog Instruction
5.1.3 OGSTOR instruction
G_OGSTOR
(9) Q66DA-G
*1
Device Item Setting data Setting range Setting side
[0]
System area
––
[1]
Completion status
The instruction completion status is stored.
0 :Normal completion
Other than 0 :Error completion (error code)
System
[2]
Pass data classification setting
The value set for pass data classification setting
[2] by the OGLOAD instruction is stored.
0H: User range setting 1 specified
1H: User range setting 2 specified
2H: User range setting 3 specified
User
[3]
System area
––
[4]
CH1 Industrial shipment settings offset value
––
System
[5]
CH1 Industrial shipment settings gain value
––
System
[6]
CH2 Industrial shipment settings offset value
––
System
[7]
CH2 Industrial shipment settings gain value
––
System
[8]
CH3 Industrial shipment settings offset value
––
System
[9]
CH3 Industrial shipment settings gain value
––
System
[10]
CH4 Industrial shipment settings offset value
––
System
[11]
CH4 Industrial shipment settings gain value
––
System
[12]
CH5 Industrial shipment settings offset value
––
System
[13]
CH5 Industrial shipment settings gain value
––
System
[14]
CH6 Industrial shipment settings offset value
––
System
[15]
CH6 Industrial shipment settings gain value
––
System
[16]
CH1 User range settings offset value
––
System
[17]
CH1 User range settings gain value
––
System
[18]
CH2 User range settings offset value
––
System
[19]
CH2 User range settings gain value
––
System
[20]
CH3 User range settings offset value
––
System
[21]
CH3 User range settings gain value
––
System
[22]
CH4 User range settings offset value
––
System
[23]
CH4 User range settings gain value
––
System
[24]
CH5 User range settings offset value
––
System
[25]
CH5 User range settings gain value
––
System
[26]
CH6 User range settings offset value
––
System
[27]
CH6 User range settings gain value
––
System
[28]
System area
––
to
[35]
*1 : Set the data only to the Pass data classification setting [2].
When the data is written to the area to be set by system, offset/gain setting value is not read properly.
s
s
s
s
b11 b10b15 b12 b9 b8 b7 b6
0 : Fixed CH6 CH5 CH4
b5 b4 b3 b2 b1 b0
CH3 CH2 CH1
to
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s