Mitsubishi Electronics MELSEC Q series MELSEC L series Home Theater Server User Manual


 
5.4 Network Dedicated Instruction
5.4.24 CCPASET instruction
5-215
G_CCPASET
5
MODULE DEDICATED
INSTRUCTION
G_CCPASET
Control Data
Device Item Setting data
Setting
range
Setting
side
[0]
Completion
status
The instruction completion status is stored.
0 : Normal completion
Other than 0 : Error completion (error code)
-System
[1]
Setting flag
Specify the validity of setting data from
to in the range from b0 to b2.
'0: Invalid' is specified, default parameter is applied.
The supplementary setting and the network operation setting in the range from b8 to bA.
-User
[2]
Total number of
slave station
Specify the number of connected slave stations. 1 to 120 User
[3]
Constant link
scan time
Set the constant link scan time.
0 : No setting
5 to 2000: Constant link scan time
5 to 2000
(ms)
User
s1
s1
s2
s4
Network configuration
setting data
0: Invalid
1: Valid
Reserved station
specification data
0: Invalid
1: Valid
Error invalid station
specification data
0: Invalid
1: Valid
Data link faulty
station setting
0: Clear
1: Hold
Output setting
in the CPU STOP status
0: Hold
1: Clear
Link scan mode
0: Asynchronous
1: Synchronous
b7
0 (Fixed)
b3 b2 b1 b0b15 b11 b10 b9 b8
0 (Fixed)
s1
s1