Mitsubishi Electronics MELSEC Q series MELSEC L series Home Theater Server User Manual


 
5.4 Network Dedicated Instruction
5.4.10 WRITE instruction
5-159
J_WRITE, G_WRITE
5
MODULE DEDICATED
INSTRUCTION
J_WRITE, G_WRITE
[5]
Target station No.
Specify the station number of the target station.
(1) Station number specification
To increase the data reliability when the station number is specified,
executing the instruction with setting Execution/Error completion type
( [0]) to '1: With arrival confirmation' is recommended.
(2) Group specification (target station is anything other than
CC-Link IE Field Network)
81H to A0H: All stations in group numbers 1 to 32
(Setting is available when Execution type is set to '0: Without
arrival confirmation' in [0].)
(3) All stations specification
FFH: All stations of the target network number (Except the host
station.)
(Setting is available when Execution type is set to '0: Without
arrival confirmation' in [0].)
To specify a group or all stations.
• Specify '0000H' or '03FFH' for the target station's CPU type ( [3]).
• Group specification cannot be set for the station of the CC-Link IE
Field Network.
• It cannot be confirmed if the data are written to the target station
normally. Confirm the device of the target station of the write
destination.
1 to 120,
125 (7DH)
81H to A0H,
FFH
User
[6]
(Fixed value)
0User
[7]
Number of resends
For instruction execution
Specify the number of instruction resends when the instruction is not
completed within the monitoring time specified in [8]. (Setting is
available when Execution type is set to '1: With arrival confirmation' in
[0].)
0 to 15 User
At instruction completion
The number of resends (result) is stored. (Setting is available when
Execution type is set to '1: With arrival confirmation' in [0].)
System
Device Item Setting data Setting range Setting side
s1
Setting value Description
MELSECNET/H 1 to 64
Ethernet
CC-Link IE Controller Network
1 to 120
CC-Link IE Field Network -
Master station 125 (7DH)
Local station or the intelligent device
station
1 to 120
s1
s1
Group No.1 81H
Group No.2 82H
Group No.32 A0H
to
s1
s1
s1
s1
s1
s1
s1