Mitsubishi Electronics MELSEC Q series MELSEC L series Home Theater Server User Manual


 
5.4 Network Dedicated Instruction
5.4.24 CCPASET instruction
5-219
G_CCPASET
5
MODULE DEDICATED
INSTRUCTION
G_CCPASET
[ST]
IF( Var_Flag_Exe = TRUE ) (* Execution flag *)
MOV( TRUE, H107, Var_ControlData[1]); (* Sets control data *)
MOV( TRUE, 3, Var_ControlData[2]);
MOV( TRUE, 0, Var_ControlData[3]);
(* Sets data of network configuration setting *)
MOV( TRUE, H2101, Var_NetworkStruct[0] );
MOV( TRUE, H0, Var_NetworkStruct[1] );
MOV( TRUE, 32, Var_NetworkStruct[2] );
MOV( TRUE, H0, Var_NetworkStruct[3] );
MOV( TRUE, 16, Var_NetworkStruct[4] );
MOV( TRUE, H2102, Var_NetworkStruct[5] );
MOV( TRUE, H20, Var_NetworkStruct[6 ] );
MOV( TRUE, 32, Var_NetworkStruct[7] );
MOV( TRUE, H10, Var_NetworkStruct[8] );
MOV( TRUE, 16, Var_NetworkStruct[9] );
MOV( TRUE, H2103, Var_NetworkStruct[10] );
MOV( TRUE, H40, Var_NetworkStruct[11] );
MOV( TRUE, 32, Var_NetworkStruct[12] );
MOV( TRUE, H20, Var_NetworkStruct[13] );
MOV( TRUE, 16, Var_NetworkStruct[14] );
END_IF;
IF( Var_Flag_Exe = TRUE ) (* Execution flag *)
MOV( TRUE, H4, Var_ReservStData[0] );
(* Sets data of reserved station specification *)
END_IF;
IF( Var_Flag_Exe = TRUE ) (* Execution flag *)
MOV( TRUE, H4, Var_ErrorInvalidData[0] );
(* Sets data of error invalid station setting *)
END_IF;
IF( Var_Flag_Exe = TRUE ) (* Execution flag *)
GP_CCPASET(TRUE, H0, Var_ControlData, Var_NetworkStruct, Var_ReservStData,
Var_ErrorInvalidData, Var_Result); (* Performs writing *)
RST( TRUE, Var_Flag_Exe ); (* Turns execution flag OFF *)
END_IF;
IF(Var_Result[0]=TRUE)THEN (*Execution finished *)
IF(Var_Result[1]=FALSE)THEN(* Normal completion *)
ELSE (* Error completion *)
END_IF;
END_IF;
(* Process on normal completion *)
(* Process on error completion *)