5.4 Network Dedicated Instruction
5.4.7 RLPASET instruction
G_RLPASET
Control Data
*1 : For the setting data for which invalid is specified, default parameter is applied.
*2 : Setting a value outside the setting range results in error completion of the instruction.
Device Item Setting data
Setting range
*2
Setting side
[0]
Completion status
The instruction completion status is stored.
0 : Normal completion
Other than 0 : Error completion (error code)
System
[1]
Setting flag
Specify the validity of each setting data from to .
0: Invalid
*1
1: Valid
User
[2]
Number of connected
modules
Set the number of connected slave stations.
1 to 64 User
[3]
Number of retries
Set the number of retries to be performed to a communication error
station.
1 to 7 User
[4]
Number of automatic
return modules
Set the number of slave stations that can be returned in one link scan.
1 to 10 User
[5]
Operation specification
when CPU is down
Specify the data link status when a master station programmable
controller CPU error occurs.
0: Stop
1: Continue
0, 1 User
[6]
Scan mode specification
Specify the link scan mode for sequence scan.
0: Asynchronous
1: Synchronous
0, 1 User
[7]
Delay time specification
Set '0' for the delay time.
0User
s1
s1
s2
s5
Send/receive and auto-refresh buffer
assignment data
Error invalid station specification data
Reserved station specification data
Slave station setting data
Mode
00: Remote net (Ver. 1 mode)
01: Remote net (Additional mode)
10: Remote net (Ver. 2 mode)
11: Cannot be used
b15b14 b3 b2 b1 b0b4
b13
0
to
0
s2
s3
s4
s5
s1
s1
s1
s1
s1
s1