5.4 Network Dedicated Instruction
5.4.13 RECV instruction
5-177
J_RECV, G_RECV
5
MODULE DEDICATED
INSTRUCTION
J_RECV, G_RECV
*1 : Data are stored only when 1 is set in bit 7 of Error completion type ( [0]).
[9]
Receive data length
The number of received data stored in to + n is stored.
0 : No receive data
1 to 960 : Number of words of receive data
System
[10]
(Reserved)
––
[11]
Clock set flag
*1
Valid/invalid status of the data in the area starting from [12] is stored.
0: Invalid
1: Valid
System
[12]
to
[15]
Clock data at the time of
error completion
*1
Clock data at the time of error completion are stored in BCD format.
System
[16]
Error-detected network No.
*1
Network number of the station where an error was detected is stored.
(However, when an error was detected at the host station, the network
number is not stored.)
1 to 239: Network number
System
[17]
Error-detected station No.
*1
Number of the station where an error was detected is stored.
(However, when an error was detected at the host station, the network
number is not stored.)
System
Device Item Setting data Setting range Setting side
s
d1
d1
s
s
s
s
s
b15 b8 b7to b0to
s
s
s
s
Month (01
H
to 12
H
)
Hour (00
H
to 23
H
)
Second (00
H
to 59
H
)
Year (00
H
to 99
H
) First two digits
Year (00
H
to 99
H
) Last two digits
Day (01
H
to 31
H
)
Minute (00
H
to 59
H
)
Day of week (00
H
to 06
H
)
00
H (Sun.) to 06H (Sat.)
[12 ]
[13 ]
[14 ]
[15 ]
s
s
Setting value Description
MELSECNET/H 1 to 64
Ethernet
CC-Link IE Controller Network
1 to 120
CC-Link IE Field Network -
Master station 125 (7DH)
Local station or the intelligent device
station
1 to 120
s