100
(5) When the shift function is set enabled
When a value is set to CH Shifting set value (RWw6 to RWw9), the value with the shifting set value added is
the target for the alert.
(6) Setting procedure
1. Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window Select a D/A converter module in "List of stations".
[CC IE Field Configuration] [Online] [Parameter Processing of Slave Station]
2. Set "CH D/A conversion enable/disable setting" to "0: Enable".
3. Set "CH Alert output setting" to "0: Enable".
4. Set values for "CH Alert output upper limit value" and "CH Alert output lower limit value".
Item Setting range
CH Alert output upper limit value
-32768 to 32767
CH Alert output lower limit value