Mitsubishi Electronics -NZ2GF2B-60DA4 Universal Remote User Manual


 
168
(8) Digital output HOLD/CLEAR setting (address: 0011
H
)
The output HOLD/CLEAR status of the extension output module is set.
For the output HOLD/CLEAR setting function, refer to the following.
CC-Link IE Field Network Remote I/O Module User's Manual
(a) Enabling the setting
Turn on and off Initial data setting request flag (RY9).
(b) Default value
The default value is CLEAR (0
H
).
If no extension output module is connected, the setting in this area is ignored.
When the data other than above is set, the D/A converter module operates with the setting value of the lower 1 bit.
(9) D/A conversion enable/disable setting (address: 0102
H
)
The D/A conversion enable/disable status is set for each channel.
(a) Enabling the setting
Turn on and off Initial data setting request flag (RY9).
(b) Default value
The default value is set to D/A conversion disable (1) for all channels.
Digital output HOLD/CLEAR setting Setting value
CLEAR
0
H
HOLD
1
H
0: D/A conversion enable
1: D/A conversion disable
Data for b4 to b15 are fixed to "0".
b0b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1
000000000000
CH3CH4 CH2 CH1