Mitsubishi Electronics -NZ2GF2B-60DA4 Universal Remote User Manual


 
156
Appendix 1.2 Remote output signals
(1) Initial data setting request flag (RY9)
Turn on this signal after writing parameter data to the remote buffer memory.
Initial data setting completed flag (RX9) turns on when the operating condition is changed.
For the on and off timing, refer to the following.
Initial data setting completed flag (RX9) ( Page 152, Appendix 1.1 (2))
(2) Error clear request flag (RYA)
This signal is used to clear Error flag (RXA) and Latest error code (RWr0).
(a) When a moderate error occurs
When this signal is turned on after the cause of the error is eliminated, the error status is cleared and Error flag
(RXA) turns off.
If the signal is turned off before Error flag (RXA) turns off, Error flag (RXA) cannot be turned off.
For the on and off timing, refer to the following.
Error flag (RXA) ( Page 153, Appendix 1.1 (3))
(b) When a major error occurs
Error flag (RXA) cannot be turned off even if this signal is turned on and off.
For the on and off timing, refer to the following.
Error flag (RXA) ( Page 153, Appendix 1.1 (3))
(3) CH Output enable/disable flag (RY10 to RY13)
Set whether to output the D/A conversion value or the offset value for each channel.
ON: D/A conversion value
OFF: Offset value
(a) D/A conversion speed
Regardless of turning on this signal, 100µs × the number of conversion enabled channels is applied.
(4) Trigger output request (RY19)
In the trigger output mode, D/A conversion is performed by turning on Trigger output request (RY19).
For the timing of turning on and off the signal, refer to the following.
Trigger output completed flag (RX19) ( Page 154, Appendix 1.1 (5))
(5) Trigger output completed clear request (RY1A)
When Trigger output completed clear request (RY1A) is turned on while Trigger output completed flag (RX19) is
on, Trigger output completed flag (RX19) is cleared.
For the timing of turning on and off the signal, refer to the following.
Trigger output completed flag (RX19) ( Page 154, Appendix 1.1 (5))
(6) Alert output clear request flag (RY1E)
Turn on and off this signal to clear an alert output.
For the on and off timing, refer to the following.
Alert output signal (RX1E) ( Page 155, Appendix 1.1 (6))