CHAPTER 8 FUNCTION
8
8.13 CC-Link IE Field Network Synchronous Communication Function
(5) Setting procedure (D/A converter module)
1. Select a D/A converter module in "List of stations" on the "CC IE Field Configuration" window, and
set the values as follows.
• Set 17 or larger number in "STA#".
• Set 32 in "Points" of "RX/RY Setting".
• Set 16 in "Points" of "RWw/RWr Setting".
2. Display the "Parameter Processing of Slave Station" window and set "Parameter write" for
"Method selection".
"CC IE Field Configuration" window Select a D/A converter module in "List of stations". [CC
IE Field Configuration] [Online] [Parameter Processing of Slave Station]
3. Set "Mode switch" to "9: Automatical judgment mode".
4. Set "CH D/A conversion enable/disable setting" to "0: Enable".
5. Click the button to write the parameter to the D/A converter module.
6. Check that "0920
H
" is stored in Latest warning code (RWr1).
[Online] [Monitor] [Device/Buffer Memory Batch]
7. The D/A converter module starts operating in the synchronous communication mode by turning
off and on the power or performing the remote reset.