CHAPTER 8 FUNCTION
8
8.10 Digital Value Range Check Function
(6) Operation example of the check code detection
Ex.
When values are set for a channel with output range of -10 to 10V as follows:
•"CH Scaling enable/disable setting": "0: Enable"
•"CH Scaling upper limit value": 24000
•"CH Scaling lower limit value": -24000
•"CH Shifting set value (RWw6 to RWw9)": -200
Controlled by the program
Controlled by the D/A
converter module
ALM LED
Remote READY (RXB)
Time
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
16383
-16384
24575
Setting range
The check code is reset
when the value is within the
setting range.
The check code is not reset
when the value is out of the
setting range.
Error clear request flag (RYA)
Warning flag (RX7)
Latest warning code (RWr1)
CH1 Set value check code (RWr2)
The error of the check code is output
when the value in CH1 Digital value
(RWw2) is greater than 24575.
Digital value
The value to be set to CH1 Digital value (RWw2)
The value after the addition of
a shifting set value and the
scaling conversion
0000
H 000FH 00FFH 0000H
0000H 0601H 0000H
-24576
OFF Flashing OFF