CHAPTER 3 SPECIFICATIONS
3
3.1 General Specifications
CHAPTER 3 SPECIFICATIONS
This chapter describes the specifications of the D/A converter module.
3.1 General Specifications
*1 Do not use or store the D/A converter module under pressure higher than the atmospheric pressure of altitude 0m.
Doing so may cause malfunction. When using the D/A converter module under pressure, please consult your local
Mitsubishi representative.
*2 If the environment satisfies the operating ambient temperature, operating ambient humidity and other conditions, the
module can be used even outside the control panel.
*3 This indicates the section of the power supply to which the equipment is assumed to be connected between the public
electrical power distribution network and the machinery within premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand
level for the equipment with the rated voltage of 300V or less is 2500V.
*4 This index indicates the degree to which conductive material is generated in terms of the environment in which the
equipment is used.
Pollution degree 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensing must
be expected occasionally.
Item Specifications
Operating
ambient
temperature
0 to 55°C
Storage ambient
temperature
-25 to 75°C
Operating
ambient humidity
5 to 95%RH, non-condensing
Storage ambient
humidity
Vibration
resistance
Compliant with
JIS B 3502 and
IEC 61131-2
Frequency
Constant
acceleration
Half amplitude
Number of
sweeps
Under
intermittent
vibration
5 to 8.4Hz - 3.5mm 10 times each in
X, Y, and Z
directions
8.4 to 150Hz
9.8m/s
2
-
Under continuous
vibration
5 to 8.4Hz - 1.75mm
-
8.4 to 150Hz
4.9m/s
2
-
Shock resistance
Compliant with JIS B 3502 and IEC 61131-2 (147m/s
2
, 3 times each in X, Y, and Z directions)
Operating
atmosphere
No corrosive gases
Operating
altitude
*1
0 to 2000m
Installation
location
Inside a control panel
*2
Overvoltage
category
*3
II or less
Pollution
degree
*4
2 or less
Equipment class Class I