Mitsubishi Electronics -NZ2GF2B-60DA4 Universal Remote User Manual


 
181
APPENDICES
A
Appendix 7 EMC and Low Voltage Directives
Appendix 7.1 Measures to comply with the EMC Directive
(b) Immunity requirements
*1 The module is an open type device (a device designed to be housed in other equipment) and must be installed inside a
conductive control panel. The tests were conducted with the programmable controller installed in a control panel.
*2 The accuracy of an analog-digital converter module may temporarily vary within ±10%.
Specification Test item Test details Standard value
EN61131-2: 2007
EN61000-4-2
Electrostatic discharge
immunity
*1
Immunity test in which
electrostatic is applied to
the cabinet of the
equipment.
• 8kV Air discharge
• 4kV Contact discharge
EN61000-4-3
Radiated, radio-frequency,
electromagnetic field immunity
*1
Immunity test in which
electric fields are irradiated
to the product.
80% AM modulation@1kHz
• 80M-1000MHz: 10V/m
• 1.4G-2.0GHz: 3V/m
• 2.0G-2.7GHz: 1V/m
EN61000-4-4
Electrical fast transient/burst
immunity
*1
Immunity test in which burst
noise is applied to the
power line and signal line.
• AC/DC main power, I/O power, AC I/O
(unshielded): 2kV
• DC I/O, analog, communication: 1kV
EN61000-4-5
Surge immunity
*1
Immunity test in which
lightning surge is applied to
the power line and signal
line.
• AC power line, AC I/O power, AC I/O
(unshielded): 2kV CM, 1kV DM
• DC power line, DC I/O power: 0.5kV CM, DM
• DC I/O, AC I/O (shielded), analog
*2
,
communication: 1kV CM
EN61000-4-6
Immunity to conducted
disturbances, induced by radio-
frequency fields
*1
Immunity test in which high
frequency noise is applied
to the power line and signal
line
0.15M-80MHz,
80% AM modulation @1kHz, 10Vrms
EN61000-4-8
Power-frequency magnetic field
immunity
*1
Immunity test in which the
product is installed in
inductive magnetic field
50Hz/60Hz, 30A/m
EN61000-4-11
Voltage dips and interruption
immunity
*1
Immunity test in which
power supply voltage is
momentarily interrupted
• Apply at 0%, 0.5 cycles and zero-cross point
• 0%, 250/300 cycles (50/60Hz)
• 40%, 10/12 cycles (50/60Hz)
• 70%, 25/30 cycles (50/60Hz)