Mitsubishi Electronics -NZ2GF2B-60DA4 Universal Remote User Manual


 
135
CHAPTER 11 TROUBLESHOOTING
11
11.1 Checking for the Error Codes and the Alarm Codes
CHAPTER 11 TROUBLESHOOTING
This chapter describes errors that may occur while the D/A converter module is used, and those troubleshooting.
11. 1 Checking for the Error Codes and the Alarm Codes
Error codes can be checked by any of the following methods:
Checking by executing a command of the slave station ( Page 135, Section 11.1 (1))
Checking by Latest error code (RWr0) ( Page 137, Section 11.1 (2))
Checking by Latest warning code (RWr1) ( Page 137, Section 11.1 (3))
Alarm codes can be checked by any of the following methods:
Checking by executing a command of the slave station ( Page 135, Section 11.1 (1))
Checking by Latest warning code (RWr1) ( Page 137, Section 11.1 (3))
(1) Checking by executing a command of the slave station
This section describes how to check the errors by executing a command of the slave station.
1. Select the D/A converter module in "List of stations"
on the "CC IE Field Configuration" window.
2. Open the "Command Execution of Slave Station"
window.
[CC IE Field Configuration] [Online]
[Command Execution of Slave Station]
3. Set "Method selection" to "Error history read" and
click the button.
List of
stations