2: When values are set for a channel with output range of -10 to 10V as follows:
•"CH Scaling enable/disable setting": "0: Enable"
•"CH Scaling upper limit value": 12000
•"CH Scaling lower limit value": 4000
The digital values and scale-converted digital values are as follows:
Digital value
Digital value after scale
conversion
Analog output voltage (V)
4000 -16000 -10
6000 -8000 -5
8000 0 0
10000 8000 5
12000 16000 10
10V
-10V
Analog output voltage (V)
Scaling lower limit
value: 4000
Scaling upper limit
value: 12000
0 16000-16000
8000
16383-16384
Scale converted digital value
Digital value