Mitsubishi Electronics -NZ2GF2B-60DA4 Universal Remote User Manual


 
174
(a) Initializing the parameter area
The parameters stored in a nonvolatile memory are set back to their default values when Commanded (1) is set
in this area.
(b) Default value
The default value is set to Not commanded (0).
Even if Parameter area initialization command (address: 1002
H
) is executed, the following remote input signals are not
cleared.
Warning flag (RX7)
Error flag (RXA)
Alert output signal (RX1E)
In addition, Remote READY (RXB) does not turn on.
After Parameter area initialization command (address: 1002
H
) is performed, the D/A converter module operates normally by
turning off and on the module.
(20)Parameter area initialization completed (address: 1003
H
)
This remote buffer memory shows the clear completed status of the parameter stored in the nonvolatile memory.
(a) Initializing the parameter area
When the parameters stored in a nonvolatile memory are set back to their default values, the value in this area
changes to Completed (1). For the timing of turning the bit Not performed (0) Completed (1) Not
performed (0), refer to the following.
Parameter area initialization command (address: 1002
H
) ( Page 173, Appendix 3 (19))
(b) Default value
The default value is set to Not performed (0).
Controlled by the D/A converter module
Parameter of nonvolatile memory
Parameter area initialization command
(address: 1002
H)
Parameter area initialization completed
(address: 1003
H)
Controlled by the program
Set parameter Default value
Not
commanded (0)
Not
commanded (0)
Commanded (1)
Not
performed (0)
Not performed (0)
Completed
(1)
Data for b1 to b15 are fixed to "0".
b0b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1
00000000000000 0
0: Not performed
1: Completed