Mitsubishi Electronics -NZ2GF2B-60DA4 Universal Remote User Manual


 
139
CHAPTER 11 TROUBLESHOOTING
11
11.2 Error Code List
0130
H
Moderate error
Non-volatile
memory data
error
(parameter)
The parameter data stored in the
non-volatile memory are
abnormal.
• Set no request (0), request (1), and no
request (0) in Parameter information clear
request (address: 1002H) and set the
parameters of the non-volatile memory to
default.
• Set the parameters again.
• Take measures against noise with a
shielded cable for connection.
• If this error persists, the module may be in
failure. Please consult your local Mitsubishi
representative.
0140
H
Minor error
Non-volatile
memory data
error (error
history)
The error history data stored in
the non-volatile memory are
abnormal.
• The module will be automatically recovered
immediately after the error occurs. Note
that the error history of the errors that have
occurred will be lost.
• Take measures against noise with a
shielded cable for connection.
• If this error persists, the module may be in
failure. Please consult your local Mitsubishi
representative.
0150
H
Minor error
Incorrect
network
parameter
access error
Access to D/A converter module
when network parameter was in
the incorrect status.
Please reset network parameter correctly.
0160
H
Minor error
Remote buffer
memory
access error
A buffer memory area other than
the remote buffer memory areas
has been accessed using the
REMFR/REMTO instruction.
Correct the setting data of the
REMFR/REMTO instruction to access the
remote buffer memory.
017
H
Moderate error
External signal
assignment
setting error
An address other than those
assigned to the extension I/O
module for the external signal
assignment function has been
set.
represents one of the following
error types.
0: Trigger output function
2: Alert output function
3: Error output
4: Warning output
Set an address that has been assigned to the
extension I/O module for the external signal
assignment function.
0180
H
Moderate error
Same address
for the external
signal
assignment
function
The same address has been set
in multiple extension output
modules for the external signal
assignment function.
Set a unique address.
040
H
*1
Moderate error
Offset/gain
setting value
inverted
The user range setting value has
been set to a value where the
offset value is equal to or greater
than the gain value.
represents the channel
number where an error has
occurred.
Correct the setting so that the offset value is
smaller than the gain value.
Error code
(hexadecimal)
Classification Error name Description and cause Action