11.2 Error Code List
0950
H
Moderate error
Clock data
outside the
range
The clock data acquired from the
CPU module is invalid.
There may be an influence from noise or a
hardware error. If the same error occurs again
even after measures have been taken against
noise, please consult your local Mitsubishi
representative.
0960
H
Major error
Network No.
changed
through the
network
The network number has been
changed through the network.
Take measures against noise and reset the
module. If the same error occurs again, the
hardware of the module may be in failure.
Please consult your local Mitsubishi
representative.
0970
H
Major error
Station No.
changed
through the
network
The station number has been
changed through the network.
Take measures against noise and reset the
module. If the same error occurs again, the
hardware of the module may be in failure.
Please consult your local Mitsubishi
representative.
0E00
H
*3
Moderate error
RWw/RWr
setting error
RWwF/RWrF has not been set in
RWw/RWr setting when
synchronous communication
mode is activated.
Reset and turn off and on the power, or
execute remote reset to assign RWwF/RWrF
in RWw/RWr setting of network parameter.
0E10
H
*3
Moderate error
Synchronous
communication
error 1
Synchronous communication
with simple motion module did
not execute in specified interval.
Execute the followings and turn off and on the
power, or execute remote reset.
• Simple motion module setting/Operation
confirmation
• Confirmation of transmission path
0E20
H
*3
Moderate error
Operation cycle
setting error
The operation cycle that D/A
converter module does not
support is set in simple motion
module.
Recheck the operation cycle setting of simple
motion module and turn off and on the power
of D/A converter module, or execute remote
reset.
0E30
H
*3
Moderate error
Synchronous
communication
error 2
Synchronous communication
with simple motion module did
not execute in specified interval.
Execute the followings and turn off and on the
power, or execute remote reset.
• Simple motion module setting/Operation
confirmation
• Confirmation of transmission path
1F00
H
Major error
Extension
module
connected
error
An extension module that is not
supported has been connected.
Remove an extension module that is not
supported.
1F20
H
Moderate error
External power
supply OFF
error
The external power supply of the
extension output module is off
with the external power supply
monitoring function enabled.
• Check the external power supply status of
the extension output module.
• If an error occurs when the system is
started or stopped, correct the timing to
enable the external power supply
monitoring function.
1F30
H
Moderate error
Extension
module
parameter error
The parameter of the model
name that is different from the
model name of the connected
extension module has been
reflected.
Set the same type and number of points in
Extension module identification code
(address: 0200
H
) as those of the connected
extension module.
1F40
H
Moderate error
Input response
time setting
error
000b or 001b has been set in the
low 3 bits of Input response
setting (address: 0010
H
).
Set a value other than 000b and 001b to the
low 3 bits of Input response setting (address:
0010