Mitsubishi Electronics -NZ2GF2B-60DA4 Universal Remote User Manual


 
151
APPENDICES
A
Appendix 1 Details of Remote I/O Signals
Appendix 1.1 Remote input signals
APPENDICES
Appendix 1 Details of Remote I/O Signals
This section describes the details of remote I/O signals assigned to the master/local module.
The assignment of each device number is for the case when the remote I/O signals of the main module are assigned
as follows.
Remote input signal: RX0 to RX1F
Remote output signal: RY0 to RY1F
Appendix 1.1 Remote input signals
(1) Warning flag (RX7)
This signal turns on when a minor error occurs.
Five seconds after the cause of the minor error is eliminated, the value in Latest warning code (RWr1) is cleared
automatically (0000
H
is stored) and Warning flag (RX7) turns off.
Warning flag (RX7)
Latest warning code (RWr1)
The minor error is
removed.
OFF
ON
ON
OFF
0000
HError code or alarm code
Controlled by the D/A converter module
A minor error
occurred.
Remote READY (RXB)
0000
H
5 seconds
5 seconds
have passed.