(10)Setting procedure
1. Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window Select a D/A converter module in "List of stations".
[CC IE Field Configuration] [Online] [Parameter Processing of Slave Station]
2. Set "Mode switch" to "1: Trigger output mode".
3. Set "CH D/A conversion enable/disable setting" to "0: Enable".
4. Click the button to write the parameter to the D/A converter module.
5. Check that "0920
H
" is stored in Latest warning code (RWr1).
[Online] [Monitor] [Device/Buffer Memory Batch]
6. Turn off and on the module or perform the remote reset to switch the mode of the D/A converter
module to the trigger output mode.