76
Configure the offset/gain setting in accordance with the actual use situation.
Connection to the CC-Link IE Field Network is not required.
Configure the offset/gain setting in the range satisfying the following condition. When the setting value out of the range is
configured, the maximum resolution and accuracy of the module may not fall within the range shown in the following
performance specifications.
I/O Conversion Characteristic of D/A Conversion ( Page 176, Appendix 4)
Because the offset value and gain value are written to the nonvolatile memory in the D/A converter module, the set
values can be used even after the module is powered on and off.
Configure the offset/gain setting in the condition of "Offset value < Gain value".
The offset and gain values are checked in the D/A converter module when Initial data setting request flag (RY9) is turned
on and off with the user range setting 1 or user range setting 2 set to Range setting (address: 0103
H
). If a wrong condition
(offset value gain value) is set, an error occurs. The error code (040
H
) is stored in Latest error code (RWr0) when they
are checked, Error flag (RXA) is turned on, and the ERR. LED turns on.